- Audible alarm (Fuel Alarm, Sensor Out) and displayed message
- Recorded as part of the Alarm History Report
- Durable and accurate with no moving parts to wear out or stick
- Withstands harsh, even icy conditions
- Detects and pinpoints leaks quickly, accurately
- Audible and displayed alarm is triggered when liquid reaches <0.1” high
- Fits 4 – 10 foot inner diameter fiberglass tanks
Specifications
|
Fuel Compatibility |
Gas, Diesel, Kerosene, Jet Fuel, Aviation Gas, E15, Bio-Diesel 20, Bio-Diesel 100, Green Diesel, DEF, Waste Oil, Motor Oil |
|
Alarm Notification |
Normal: Sensor in Normal State – No liquid detected |
|
Liquid Alarm: Water detected |
|
|
Fuel Alarm: Fuel or Fuel / Water detected |
|
|
Sensor Out: Sensor not communicating to ATG Console |
|
|
Operating Principle |
Optical sensor and conductivity |
|
Product Activation Height |
Fuel or Water – <0.1” (0.25cm) |
|
Operating Temp |
-40 to +122°F (-40 to +50°C) |
|
Dimensions |
4.3” (11cm) length, 1.5” (3.8cm) width, 0.5” (1.3cm) thick |
|
Standard Cable |
25ft (7.6m) |
|
Tank Size |
Fits 4 to 10ft (1.2 to 3m) Inner Diameter Fiberglass Tanks |
Like this: