Containment Sump Sensor
The Solid-State Discriminating Containment Sump Sensor (794380-350) is 22.1″ (56.1cm) high, and 2.2” (5.6cm) in diameter.
|
Product Activation Height |
Gas – 0.125″ (3.175mm); |
- Ultrasonic technology determines presence of fluid and alarms at low level and high-level “trip” points
- Conductive elastomer differentiates between hydrocarbons and other liquids and alarms when hydrocarbon is detected at any point on the sensor
- Remains accurate, reliable and reusable even after exposure to heavy concentrations of hydrocarbons
- Fuel at any height on the sensor, even when floating on other liquid, triggers a fuel alarm
Specifications
|
Fuel Compatibility |
Gas, Diesel, Kerosene, Jet Fuel, Aviation Gas, E15, E85*, Bio-Diesel 20, Green Diesel, Waste Oil, Motor Oil |
|
Alarm Notification |
Normal: Sensor in Normal State – No liquid detected |
|
Low Liquid: Liquid detected above low activation minimum |
|
|
High Liquid: Liquid detected above high activation minimum |
|
|
Fuel Alarm: Permeable material saturated with fuel |
|
|
Sensor Out: Sensor not communicating with ATG Console |
|
|
Operating Principle |
Electrical conductivity / optical |
|
Operating Temp |
-40 to +122°F (-40 to +50°C) |
|